Volume 15, Issue 1 (March 2019)                   IJEEE 2019, 15(1): 14-28 | Back to browse issues page


XML Print


Download citation:
BibTeX | RIS | EndNote | Medlars | ProCite | Reference Manager | RefWorks
Send citation to:

Hajiaghasi S, Abbaszadeh K, Salemnia A. A New Approach for Transformer Interturn Faults Detection Using Vibration Frequency Analysis. IJEEE 2019; 15 (1) :14-28
URL: http://ijeee.iust.ac.ir/article-1-1228-en.html
Abstract:   (3896 Views)
Interturn fault detection is a challenging issue in power transformer protection. In this paper, interturn faults of distribution transformer are studied and a new online detection method based on vibration analysis is proposed. Transformer electromagnetic forces are analyzed by time stepping finite element (TSFE) modeling of interturn fault. Since the vibration associated with inter-turn faults is caused by electromagnetic forces, axial and radial electromagnetic forces for various interturn faults are studied. Transformer winding vibration under interturn faults is studied through an equivalent mathematical model combined with electromagnetic force analysis. The results show that it is feasible to predict the interturn winding faults of transformer windings with the transformer vibration analysis method. Simulation and experimentation studies are carried out on 20/0.4 kV, 50 kVA distribution transformer. The results confirm the effectiveness of the proposed method.
Full-Text [PDF 1913 kb]   (3406 Downloads)    
Type of Study: Research Paper | Subject: Power Transformers
Received: 2018/02/17 | Revised: 2019/02/07 | Accepted: 2018/06/11

Rights and permissions
Creative Commons License This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.

Creative Commons License
© 2022 by the authors. Licensee IUST, Tehran, Iran. This is an open access journal distributed under the terms and conditions of the Creative Commons Attribution-NonCommercial 4.0 International (CC BY-NC 4.0) license.