Volume 2, Issue 3 (October 2006)                   IJEEE 2006, 2(3): 131-141 | Back to browse issues page

XML Print


Download citation:
BibTeX | RIS | EndNote | Medlars | ProCite | Reference Manager | RefWorks
Send citation to:

H. Shateri, S. Jamali. Effects of CT and VT Connection Point on Distance Protection of Transmission Lines with FACTS Devices. IJEEE 2006; 2 (3) :131-141
URL: http://ijeee.iust.ac.ir/article-1-21-en.html
Abstract:   (12919 Views)
This paper presents the effects of instrument transformers connection points on the measured impedance by distance relays in the presence of Flexible Alternating Current Transmission System (FACTS) devices with series connected branch. Distance relay tripping characteristic itself depends on the power system structural conditions, pre-fault operational conditions, and especially the ground fault resistance. The structural and controlling parameters of FACTS devices as well as the connection points of instrument transformers affect the ideal tripping characteristic of distance relay. This paper presents a general set of equations to evaluate the measured impedance at the relaying point for a general model of FACTS devices to consider different affecting parameters.
Full-Text [PDF 327 kb]   (4735 Downloads)    
Type of Study: Research Paper |
Received: 2008/10/07 | Accepted: 2013/12/30

Rights and permissions
Creative Commons License This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.

Creative Commons License
© 2022 by the authors. Licensee IUST, Tehran, Iran. This is an open access journal distributed under the terms and conditions of the Creative Commons Attribution-NonCommercial 4.0 International (CC BY-NC 4.0) license.